KEW 2413F - Leakage Clamp Meters

  • Extra wide transformer jaws are best suited for clamping on all three or four wires (3phases) together for leakage current measurement.
  • Frequency filter switch to eliminate the effect of harmonics.
  • Output terminal.
  • Resolution 0.1mA.
Share:
AC A (50/60Hz) 200mA/2/20/200A/1000A
±1.5%rdg±2dgt (200mA/2/20A)
±2%rdg±2dgt (200A 0 - 500A)
±5.5%rdg (501 - 1000A)
AC A (WIDE) 200mA/2/20/200/1000A
±1%rdg±2dgt [50/60Hz],
±3%rdg±2dgt [40Hz - 1kHz] (200mA/2/20A)
±1.5%rdg±2dgt [50/60Hz],
±3.5%rdg±2dgt [40Hz - 1kHz] (200A/0 - 500A)
±5%rdg [50/60Hz],
±10%rdg [40Hz - 1kHz] (501 - 1000A)
Conductor size Ø68mm max.
Frequency response 40Hz - 1kHz
Effect of external stray magnetic field Ø15mm 100A 10mA AC max.
Output Waveform :
AC200mV against the maximum value of each range (1000A range is 100mV)
Recorder :
DC200mV against the maximum value of each range (1000A range is 100mV)
Applicable standards IEC 61010-1 CAT III 300V
IEC 61010-2-032
Power source 6F22 (9V) × 1 *Continuous measuring time: Approx. 60 hours
Dimensions 250(L) × 130(W) × 50(D)mm
Weight 570g approx.
Included Accessories 9094 (Carrying Case)
6F22 × 1
Instruction Manual
Optional Accessories 7073 (2WAY Output Cord)

7066A
Test Leads

View Detail