| Voltage Test | |
|---|---|
| Voltage Range | 12 - 690V AC/DC |
| Nominal Voltage | 12/24/50/120/230/400/690V AC (16 - 400Hz), DC (±) |
| Tolerance | Light on at more than: |
| (Threshold Voltage) | 7±3V (12V LED) 18±3V (24V LED) 37.5±4V (50V LED) 75%±5% of nominal voltage (120/230/400/690V LED) |
| Response Time | <0.6s at 100% of each nominal voltage |
| Peak Current | ls<3.5mA (at 690V) |
| Measurement Duty | 30s ON (operation time) 240s OFF (recovery time) |
| Single-pole Phase Test | |
| Voltage Range | 100 - 690V AC (50/60Hz) |
| Phase Rotation Test | |
| System | Three-phase 4-wire system 200 - 690V phase-to-phase AC (50/60Hz) |
| Phase Range | 120±5 degree |
| Continuity Test | |
| Detection Range | 0 - 400k?+50% |
| Test Current | Approx. 1.5?A (battery 3V, 0?) |
| Applicable standards | IEC 61243-3, IEC 61010-1, IEC 61557-7 CAT ? 690V / CAT ? 600V Pollution degree 2 |
|---|---|
| IP Rating | IP65 (IEC 60529) |
| Operating temperature & humidity range | -15 - 55ºC, max 85% RH (No Condensation) |
| Storage temperature & humidity range | -20 - 60ºC, max 85% RH (No Condensation) |
| Power source | LR03 (AAA) 1.5V×2 |
| Dimensions | 246(L)×64(W)×26(D) mm |
| Weight | 190g (including batteries) |
| Included Accessories | LR03 (AAA) 1.5V×2, KTA01 (4mm metal tips [2pcs/set]), KTA02 (4mm rubber caps [2pcs/set]), Instruction manual |